AUS-ETO-L2.1

Generation, paralleling, load sharing and blackout recovery

This lesson covers how on-board generation differs from shore power, the three conditions required before paralleling an alternator onto a live bus, how governors and AVRs control real and reactive load sharing, and the step-by-step sequence for blackout recovery.

Entry & progression

The ETO owns the generation plant. Everything downstream of the busbar is somebody's convenience. Everything upstream of it is the vessel's ability to stay alive.

A vessel makes its own electricity, and it makes it in a plant with no grid behind it. Ashore, if a generator drops off, the grid absorbs it and nobody notices. At sea there is no grid. The load that machine was carrying has to go somewhere in the next few hundred milliseconds, and if the remaining sets cannot take it, they trip too. That cascade is a blackout, and it is the event the whole design exists to prevent.

Paralleling — three conditions, no exceptions

The ship's electrical distribution

To bring an incoming alternator onto a live bus, three things must match the bus at the moment the breaker closes.

  1. Voltage — the incoming machine's terminal voltage matched to the bus
  2. Frequency — matched, and ideally a fraction high, so the machine walks onto load rather than motoring
  3. Phase angle — the waveforms aligned at the instant of closing, and the phase rotation the same

Close a breaker out of phase and the machine will try to snap into step with the bus instantly. The torque that produces goes through the coupling, the shaft and the foundations. Synchroscopes, check-synchronising relays and auto-synchronisers exist because human judgement at that instant is not good enough.

WARNING — Never defeat a check-sync relay to get a machine on the bus It is the last thing standing between an impatient closing and a wrecked alternator. If the synchroniser will not let you close, the reason is that closing would be wrong. Find the reason. The temptation to override arrives at exactly the moment you can least afford to be wrong — a falling bus, a guest evening, a chief on the phone.

Load sharing

Once two machines are in parallel, they must share. Real power (kW) is shared by governor characteristic — the droop or isochronous setting of each engine's speed control. Reactive power (kVAr) is shared by excitation — the AVR characteristic of each alternator.

Symptom Where to look
Machines split unequally on kW Governor droop / speed setpoint / load-sharing line
Machines split unequally on kVAr AVR voltage setpoint / excitation droop / cross-current compensation
One machine motoring (reverse power) Governor setpoint too low, or fuel starvation on that engine
Hunting between machines Governor gains, or two isochronous machines fighting without a load-share line

A machine drifting toward reverse power is not sharing badly — it is being driven by the bus, and the reverse-power relay will remove it. Watch the kW split, not just the amps.

Blackout recovery

The order of a blackout recovery

  1. Emergency source picks up its own board automatically — confirm it did, and confirm what it is feeding.
  2. Restart a generator. Air or batteries: know which, and know the state of both before you need them.
  3. Establish the bus dead and close the first machine onto a dead bus — no synchronising required.
  4. Restore essential services in order: steering, then propulsion auxiliaries, then the rest.
  5. Restore the hotel load LAST, and restore it in blocks. Throwing the whole ship back on at once is how you black out a second time.

The sequence above is not a rule of thumb. Every vessel has its own blackout recovery procedure, written to its own plant, and it is one of the very few documents you should be able to recite in the dark. Because that is when you will need it.

Practice questions

5 questions
recallcore

recall · core

The three conditions that must be satisfied before closing an incoming alternator onto a live bus are: (a) Voltage, frequency and phase angle (b) Voltage, current and power factor (c) Frequency, current and insulation resistance (d) Voltage, temperature and load

recallcore

recall · core

Unequal sharing of REAL power (kW) between two paralleled machines points first at: (a) The automatic voltage regulators (b) The reverse-power relays (c) The busbar insulation (d) The governors and the load-sharing line

recallcore

recall · core

Unequal sharing of REACTIVE power (kVAr) is corrected at: (a) The excitation / AVR characteristic (b) The governor droop setting (c) The circuit breaker trip units (d) The engine fuel rack

recallcore

recall · core

During a blackout recovery, the first generator is closed onto: (a) The bus in parallel with the emergency generator (b) A live bus, after synchronising (c) A dead bus — no synchronising is required (d) The shore supply

recallcore

recall · core

The hotel load is restored last after a blackout because: (a) It is not connected to the main switchboard (b) Guests should not notice the blackout (c) It cannot be restored until propulsion is at full power (d) Throwing the whole ship back on at once risks blacking out a second time

AI-drafted catalogue content pending SME review. Sea service and course requirements change; verify with AMSA before relying on this for a career decision.

School